Fires Happen: it’s Time to Act.

Fires Happen: it’s Time to Act.

At sea, fire pose one the of biggest threat to ships: according to Lloyds List, almost 10% of all total losses at sea for the last ten years have been caused by fire. Sailing alone and at sea throughout the year, and without the ability to call upon the emergency services as a land-based asset might. As vessels become larger and more sophisticated, a greater financial interest is tied up into one ship, meaning that the risks are magnified if the vessel would get into difficulties e.g. a fire.

“Ships are their own fire brigade”

Misunderstanding exists across parts of Shipping regarding the application of a part of the International Maritime Organisation, Safety of Life at Sea, Fire Safety Systems (IMO SOLAS FSS) Code; the need for crew to test the contents of their CO2, FM-200® & NOVEC™ 1230 Gaseous Extinguishing Systems in between the periodic inspection, maintenance and certification intervals. These periodic inspections are conducted annually or biennially, and only by an Accredited Service Agent i.e. an external Marine Servicing Company. As stated above, the reason the IMO requires crew to test for contents in-between these is that the “ship sails alone”; it must act as its own emergency fire service.

What are the risks?

A ship’s gaseous extinguishing system typically comprises between 200 and 600 cylinders each containing 45KG of CO2 under high 720 psi/ 49 bar pressure. (Other suppressant clean agents such as FM-200® and Novec™1230 are becoming more widely used.) One of the highest probabilities of discharge occurs during their maintenance. Some marine service companies estimate that 20% of a ship’s CO2 cylinders have discharged or partially leaked their contents at some point in their lifetime.

Taking CO2 systems through as an example, although random checks may be suitable in some sectors, it is worth remembering that because the normal design concentration of CO2 of 34-72 v/v % is above the nearly immediate acute lethality level, these systems have an extremely narrow safety margin. As these systems work through oxygen dilution rather than the chemical disruption of the catalytic combustion chain (which is the case with other clean agents), insufficient oxygen levels during an accidental discharge may allow a situation to spiral out of hand.

A current, widely acknowledged gap in the reliability of many marine firefighting systems is the way in which the fire suppressant levels are checked. A large number of ship operators are still relying on the crew to remove and weigh the fire suppressant containers at regular intervals in order to measure the quantity of fire suppressant. This introduces several risks associated with human error – containers could be reconnected incorrectly, crew may become bored and skip a few measurements, and accurate readings are not ensured.

 

“CO2 bottles leak”

Yet although this poses high levels of risk to the service companies and the crew, because gaseous extinguishing systems are highly pressurised, the risk of leaking and discharging is accepted as part of their use and this is shown in the regulations that demand their upkeep e.g. IMO SOLAS FSS Ch5. 2.1.1.3:

“Means shall be provided for the crew to safely check the quantity of the fire extinguishing medium in the container”

Often this is misunderstood, this code specifically states that the crew must test their extinguishing installations in between the periodic inspection, maintenance and certification. Only having the annual inspection by accredited marine servicing companies is not enough – the crew must take responsibility for its own fire protection.  Crew are often not trained or certified to shut-down, dismantle, weigh and re-install the gaseous cylinders – the traditional method. In order to mitigate this risk, technology allowing for accurate measurement and logging of agent fill levels in fire suppression systems should be used particularly if fixed firefighting systems are being relied upon without the extra layer of safety that insulation would provide.

A Call for Crew to Inspect Fire System Cylinder Contents

Using an ultrasonic liquid level indicator, the Portalevel® MAX Marine, is the only way that the crew can safely test their CO2 without disturbing them. If marine companies implemented the IMO SOLAS FSS codes by testing safely and quickly (just 30-60 seconds per cylinder) by using liquid level indicators and marine servicing companies were able to do their work without allowing for time pressures, then marine safety would be far safer.

What About Compartmentation?

Assuming fire suppressant agent fill levels are sufficient to extinguish any fire, the suppressant agent must be contained within the compartment in which the fire is present and the agent is not allowed to disperse to other compartments. In other words, if a gaseous firefighting system is in use, the reliability of such a system is critically dependent on the ability of a compartment to contain the fire suppression agent. Therefore, regardless of the standard of compartment insulation, the integrity of compartments should be verified. This is even more important on older vessels where compartment integrity may have degraded over time.

Compartment integrity is not isolated to fire containment and fire suppression but is also critically important to damage stability and compartment flooding. It is always important to verify that a vessel has been built to specification and certain safety critical aspects have not degraded over time. Compartmentation integrity must be tested so as to ensure that the design analysis for compartment flooding and damage stability reflects the true condition of the ship. It is emphasised that this is even more important on older vessels where compartment integrity may have degraded over time.

Test Your Compartmentation

Ultrasonic compartmentation integrity testers provide interpretation of the fire resistance of the desired locations, labelling them either airtight or giving an indication of the overall leakage of the compartment. In a case where there is too much leakage in a room, a Portascanner® 520 ultrasonic compartmentation integrity tester is an unrivalled ideal for the rapid and accurate  identification of these sites so that they can be sealed. It is lightweight, fast and easy to use, allowing leak site detection to increase its operational efficiency and speed to a degree that has never been seen thus far in the maritime industry.

Ensure Vessel Safety

Bad industry practice is unacceptable when fire risk may have catastrophic results due to risk to life, downtime in operation due to ship safety and repair work and incalculable reputational damage. The crew, cargo and vessel must be protected when at sea because it is it’s own fire brigade without accessibility to typical emergency services. This is a call to respond to regulations with a rigorous attitude, to go above and beyond, to provide security of life and infrastructure.

Keywords:Maritime, Fire At Sea, Fire Suppression Systems, Shipping, IMO SOLAS FSS, CO2

Request a Quotation

Online Submission

Click Here

Call: +44 207 629 8475

Our customer support line is open during UK
business hours
Mon-Friday, 9.00am - 5.00pm GMT

Email: sales@coltraco.co.uk

Enquire via email and a dedicated
member of the sales team will deal
with your request personally.

Cookies make it easier for us to provide you with our services. With the usage of our services you permit us to use cookies.
Ok