Monitor Liquid Level in Gaseous Cylinders with the Portalevel®

31˚C - CO2’s critical point: the temperature at which CO2 turns totally from liquid to gas.

CO2 is permanently under 720 psi or 49 bar of pressure ie nearly 50 times atmospheric pressure (by comparison a cup of water at sea level exists at 1 bar or 14.5 psi). Its state changes under increased temperatures to one that is neither a liquid nor a gas.

50-55˚C   -  critical points of FM-200® and Novec™1230 (turning from liquid to gas).

Gases under pressure are often effectively considered by the industry as single and passive cylinder columns of solid material from the perspective of their monitoring following installation. Whereas being under pressure and constantly changing under temperature they should be considered as active and dynamic systems requiring constant monitoring. These are not passive systems therefore; they are dynamic ones, and all dynamic systems under pressure need constant monitoring.

14520 - the ISO standard regarding fire systems from installation with regard to room integrity through to maintenance and inspection of contents

ISO 14520-1:2015(E) specifically states in 6.2.4.2 Contents Indication that - Means shall be provided to indicate that each container is correctly charged and in 9.2.1.1 At least annually, or more frequently as required by the authority, all systems shall be thoroughly inspected and tested for proper operation by competent personnel. Under ISO 14520 where gaseous extinguishing systems have to be designed in relation to the discharging agent hold-time (if the room cannot hold the agent because of leaks the agent will disperse and not extinguish the fire) and discharging agent peak pressure (if the pressure is too high for partition walls or suspended ceilings they will be blown apart or damaged and possibly destroying the room integrity). At the design stage of a fire extinguishing system rooms are tested for room integrity by positively pressurising a room and detecting escaping pressure to verify that the room itself into which the gaseous extinguishant discharges on actuation can both hold the agent after its discharge and hold its pressure on actuation. The fire system is then installed and commissioned. But over the next 10 years no further tests are made on room integrity and the cylinders merely hydrostatically tested to ensure they can cope with their design pressure limits. How can one be sure therefore that on actuation the room will hold the discharged agent to extinguish the fire and its partitions and ceilings are capable of withstanding the pressure of the agent on discharge?

5% - loss of pressure above which it is deemed unacceptable in non-liquefied gaseous extinguishing systems and thus requires refilling.

10% - loss of agent above which it is deemed unacceptable in liquefied gaseous extinguishing systems and thus requires refilling

The risks of accidental discharge or leakage is recognised.  BS EN ISO 14520 -1:2015(E) reasonably assumes that the execution of its provisions is entrusted to people qualified and experienced in the specification, design, installation, commissioning, testing, approval, inspection, operation and maintenance of systems and equipment, and who can be expected to exercise a duty of care to avoid unnecessary release of extinguishant. The assumptions in the installation, commissioning and maintenance of gaseous extinguishing systems is that they are highly pressurised but risk leaking and discharging. The regulations that sensibly underpin this assumption aim to identify their leak identification at an interval of every 6 months. Cylinders accidentally discharge. CO2 can cause fatalities if it does. 1% of pressure gauges fail and 25% of valves too. 

1.5mm - the accuracy which Portalevel® and constant monitoring Permalevel® Multiplex can find the liquid level indicator of agent in cylinders to.

62.5% - Calibration band setting on the Portalevel® Max, found to operate on the broadest range of application to the tightest tolerance of any ultrasonic liquid level indicator in the world.

26 seconds – The average test time to identify the liquid level in any liquid gaseous cylinder using the Portalevel® Max.

The UL approved Portalevel Max is designed to inspect the content of Fire Suppression System Cylinders of CO2, FM-200™, Novec 1230, FE-13, FE-25, NAF S III, CEA410, Halons and a range of other extinguishing agents. The device is a quick, accurate and efficient method of inspecting cylinder content. Portalevel® MAX builds on Coltraco Limited’s 30 years’ experience in designing, manufacturing and supporting ultrasonic level indicator.  The unrivalled quality of the Portalevel, have resulted with units operating throughout the world

 

CEO Message

Integrity and Science Key to Our Culture of Performance

Dear Coltraco Customers, Strategic Partners and Distributors,

Integrity is our defining value. Performance is its consequence. We understand that our customers have choices, and how we perform determines whether customers choose us. Coltraco’s Code of Ethics does not merely require compliance with laws. It embodies a Commitment to positive behaviours that build trust, promote respect, operate with distinction, with courtesy and global levels of performance, demonstrating our integrity and delivering customer performance.

We honour our commitments, communicate transparently, and act with honour. Ethics are the foundation of our performance culture and our science-based approach. We lead in specific technologies delivering the watertight integrity monitoring of marine structures and the monitoring of fixed liquefied gaseous fire extinguishing systems and the room integrity of protected space to ensure agent hold-times post-installation. We show this by our understanding of the science in them and the mathematics that explain them.

I would like to thank you for your business and for the relationships with our Customers, Strategic Partners, Distributors and ODAs who we value so highly.

My kindest regards,
Carl

Carl Stephen Patrick Hunter BA(Dunelm) Hon DSc FRINA FIMarEST MRAeS
CEO & Managing Director
Coltraco Ultrasonics Limited
46-47 Mount Street, Mayfair, London W1K 2SA
United Kingdom

Tel:  +44 20 7629 8475
Fax: +44 20 7629 8477

Call Now : +44 207 629 8475

 

References in PDF Format

 

Underwriters LaboratoriesUnderwriters Laboratories

 

Reference Alpha Fire UK Portalevel MAX Sept 2012

Reference Portascanner-II CSD MOD Albion and Bulwark

Quotation.

Quotation

Support.

Support

About Coltraco Ltd.

About

 
 

Request a Quotation

Online Submission

Click Here

Call: +44 207 629 8475
Our customer support line is open during UK
business hours
Mon-Friday, 9.00am - 5.00pm GMT

Email: sales@coltraco.co.uk
Enquire via email and a dedicated
member of the sales team will deal
with your request personally.